Device Remote Upgrade

Download the upgrade package from EnOS Cloud and push it to the target device or sub-device for upgrade

Application


Edge OTA Function Scope

Edge Logger

Edge IIoT Gateway & Extensive

Lift Box

Logger EMS

Edge software remote upgrade

×

operating system vulnerability remote upgrade

Application software upgrade

×

Sub-device firmware upgrade(HTTP)

Sub-device firmware upgrade(Serial Port)

×

Features

  • Support the upstream and downstream upgrade channels

  • Firmware integrity verification

  • Firmware upgrade judgment

  • Provide Open API for sub-device upgrade

    • Support sub-device report and query versions

    • Provide firmware download channel

    • Push the upgrade command to sub-device

    • Obtain the upgrade result and report to EnOS Cloud

Use Path

EnOS Edge OTA

For OTA process of intelligent gateway (device), please refer to EnOS Cloud Firmware Upgrade OTA

Sub Equipment OTA

Step1 Develop Sub Equipment OTA Capability

The upgrading of OTA at the sub device end largely depends on the physical space and function realization of the device itself:

  • The sub device establishes an HTTP upgrade channel or serial port connection with EnOS edge

  • The sub device can obtain its own firmware version information and report it to EnOS edge

  • The sub device needs to manage its version number independently

  • The sub equipment needs to define the upgrade progress independently

  • The sub device needs to independently verify the firmware integrity ability. If it fails in the upgrade process, the sub device can automatically rollback to the version before the upgrade

Note

Under the serial port upgrade channel, up to 5 sub devices are upgraded at the same time. It is recommended to delete “upgrade” after the upgrade to avoid occupying edge resources.

Step2 Add Upgrade Sub Device

  1. Log in to the EnOS Portal and select edge Management > edge details > OTA upgrade from the left navigation bar.

  2. Click add device and select the sub device to be upgraded according to the prompts on the page to add it.

  3. Fill in SN serial number to distinguish equipment.

../_images/firmware.png

Note

Fill in SN serial number to ensure that it is consistent with the Sn content reported by the interface; You can also fill in the unique identification ID of the sub equipment.

Step3 Add Firmware Upgrade

The Edge follows the IoT Hub firmware remote upgrade process to perform OTA upgrades on behalf of sub-devices. After completing the above steps to develop sub device OTA capabilities and add upgraded devices, please refer to Firmware Wireless (OTA) Upgrade for subsequent firmware wireless (OTA) upgrades.